Open field tools

14 field tools for the next service call.

Practical tools for technicians, estimators, and owners. No account required. Use them in the field, then come back when you need the operating system behind the work.

Built for real decisions: fast estimates, transparent assumptions, and results you can explain to a customer or a teammate.

01 / Sizing

Heat load

Heat Load Calculator

Simplified Manual J–style heating & cooling load estimate.

Cooling design

Heating design

Estimated load

25,885

Btu/h cooling

2.2 tons

26,567

Btu/h heating

26.6 MBH

Sensible: 20,679 Btu/hLatent: 5,206 Btu/h
Cooling load breakdown
Walls2,092 Btu/h
Roof / ceiling3,312 Btu/h
Windows (conduction)2,156 Btu/h
Windows (solar)6,600 Btu/h
Infiltration3,499 Btu/h
People & appliances3,020 Btu/h
Latent (moisture)5,206 Btu/h

Quick estimate for sizing discussions only. A full room-by-room ACCA Manual J load calculation is required for permit and equipment selection.

02 / Flow

Hydronics

Hydronics

Flow, heat load & pipe sizing for water and glycol loops.

Water · cp 4.19 kJ/kg·K · ρ 992 kg/m³

Result

6

GPM flow

60,000

Btu/h load

Pipe sizing

2.4fps

Velocity

9.1ft/100ft

Head loss

Ideal range

Estimates use the standard q = ṁ·cp·ΔT relationship and Hazen-Williams (C=140) for pressure drop. Verify against manufacturer data and confirm glycol properties at your operating temperature.

04 / Refrigeration

Pressure–Temperature Chart

PT Chart

Refrigerant pressure ↔ saturation temperature reference.

Temp unit
Pressure unit

Result

Liquid pressure (bubble)118.3 psig

Use for subcooling on the liquid line

Vapor pressure (dew)118.3 psig

Use for superheat on the suction line

Field-reference approximations at sea level. Always verify against the manufacturer's official PT chart for critical work.

05 / Refrigeration

Superheat & subcooling

Gauge readings

Metering device

Target superheat (fixed orifice)

Measured

12.1 °F

Superheat

Sat 39.9°F (dew)

14.8 °F

Subcooling

Sat 104.8°F (bubble)

Target superheatN/A

Target-superheat charging applies only to fixed-orifice systems. Charge TXV/EEV systems to subcooling per the dataplate.

Superheat uses the dew curve; subcooling uses the bubble curve. Always confirm charge against the equipment charging chart before adding or recovering refrigerant.

06 / Airflow

Ductulator

Ductulator

Equal-friction duct sizing. Results update live as you adjust the dials.

400 CFM
0.08 in wg/100 ft

Residential supply is typically 0.08–0.10 in wg/100 ft.

Round duct

10.3"

Exact diameter

12"

Nearest standard

Velocity (12" duct)509 FPM

Low — supply branch OK

Rectangular equivalents

Size (W × H)Velocity
16" × 6"600 FPM
11" × 8"655 FPM

07 / Air properties

Psychrometric chart

Psychrometric Chart

Pick any two known properties and solve the complete air state.

°F
%

Barometric pressure 101.33 kPa (29.92 inHg)

Air properties

Dry bulb
75.0 °F
Wet bulb
62.6 °F
Dew point
55.2 °F
Rel. humidity
50.0 %
Humidity ratio
64.6 gr/lb
Enthalpy
28.1 BTU/lb
Specific vol.
13.68 ft³/lb
Vapor press.
1.48 kPa

Tip: click anywhere on the chart to drop a state point.

32415059687786951041131220357010514017521010%20%30%40%50%Dry-bulb temperature (°F)Humidity ratio (gr/lb)

08 / Air properties

Mollier h-x diagram

Mollier h-x Diagram

The European/UK enthalpy–humidity chart. Pick any two known properties to solve the complete air state.

°C
%

Barometric pressure 101.33 kPa (1013.3 mbar)

Air properties

Dry bulb
22.0 °C
Wet bulb
15.4 °C
Dew point
11.1 °C
Rel. humidity
50.0 %
Humidity ratio
8.2 g/kg
Enthalpy
43.0 kJ/kg
Specific vol.
0.85 m³/kg
Vapor press.
1.32 kPa

Tip: click anywhere on the chart to drop a state point.

10%20%30%40%50%-10-505101520253035404550051015202530Humidity ratio (g/kg)Dry-bulb temperature (°C)Dashed = constant enthalpy (kJ/kg)

09 / Electrical

Wire sizing

Wire Sizing

NEC conductor sizing by ampacity and voltage drop for copper and aluminum.

Voltage drop uses 2× R·I·L. Length is one-way circuit distance.

Recommended size

8

AWG / kcmil

50

A ampacity

6.1V

Voltage drop

2.55%

Drop at load

Carries 40 A within 3% voltage drop over 100 ft.
Ampacity reference (Copper, 75°C)
SizeAmpacityΩ/1000ft
1420 A3.07
1225 A1.93
1035 A1.21
850 A0.764
665 A0.491
485 A0.308
3100 A0.245
2115 A0.194
1130 A0.154
1/0150 A0.122
2/0175 A0.0967
3/0200 A0.0766
4/0230 A0.0608
250255 A0.0515
300285 A0.0429
350310 A0.0367
400335 A0.0321
500380 A0.0258

Based on NEC Table 310.16 ampacities and Chapter 9 resistance values. Does not apply ambient or conduit-fill derating. Always verify against the current NEC and your AHJ.

10 / Airflow

Airflow & delivered capacity

Measured airflow

Coil entering / leaving air

Airflow

900 FPM

Avg velocity

1.11 ft²

Free area

1000 CFM

Airflow

Delivered capacity

23,760 Btu/h

Sensible

9,928 Btu/h

Latent

34,479 Btu/h

Total

2.87 tons

Delivered

Sensible heat ratio69%

Delivered capacity reflects measured air only. Confirm against equipment rated capacity and superheat/subcooling before drawing conclusions.

11 / Airflow

Duct system designer

Blower & measured static

Static pressures in inches of water column (in. wg).

Component pressure drops

Effective length

Design targets

0.04"

Available static

0.020

Target friction /100 ft

Total effective length200 ft

Friction rate is low — ducts will be large. Acceptable for quiet, low-static systems.

Blower check

Measured vs. rated ESPOver rated ESP

Trunk preview

Round trunk at target friction20.5" → 22"

12 / Electrical

Electrical service

Line-to-line voltage

Power

Motor FLA check

Results

Voltage imbalance

1.27%Investigate (>1%)

Avg 472 V · max deviation 6 V

Power

19.12 kVA

Apparent

16.44 kW

Real

Motor FLA

86%Within range

of nameplate FLA

NEMA MG-1: derate above 1% voltage imbalance and do not operate above ~5%. De-energize and follow lockout/tagout before servicing.

13 / General

Unit converter

Unit Converter

HVAC/R field measurement conversions.

1 Fahrenheit (°F)

-17.2222

Celsius (°C)

Temperature chart

1 Fahrenheit (°F) equals:

Fahrenheit (°F)1
Celsius (°C)-17.2222
Kelvin (K)255.9278
Rankine (°R)460.67

Conversions use standard reference factors. US (short) tons and US gallons are used for weight and liquid flow. Verify critical values against manufacturer documentation.

14 / Rigging

Crane & lifting

Crane Lifting

Sling leg tension and crane capacity check for equipment lifts.

Sling angle from horizontal: 60°
60°LOAD
Lower sling angles dramatically increase leg tension. 30° is the typical minimum allowed. A 4-leg sling on a rigid load is rated as 3 legs unless equalized.

Lift analysis

Within capacity

70% of rated capacity (8,400 lb gross)

3,233

lb tension / leg

1.155

Angle load factor

3 effective legs

2,800lb

Vertical / leg

1,617lb

Inward side load

3,600 lb of capacity remaining.

Field-reference only. Verify against sling capacity tags, the crane load chart at the actual working radius, and a qualified rigging plan. Capacity must account for boom length, radius, and outrigger setup.